With the increasing adoption of innovative architectural forms, the use of sloped beam-to-column connections in buildings and special steel structures has become more widespread. In steel moment-resisting frames with sloped beams, Reduced Beam Section (RBS) connections can be used to relocate the plastic hinge away from the beam-to-column interface, thereby enhancing the ductility and seismic performance of the frame. Previous studies have shown that as the beam slope increases, the stress distribution within the reduced beam section changes, resulting in stress concentration around the heel and toe regions of the beam. This study experimentally investigates the cyclic behavior of steel RBS beams with stiffened bolted extended end-plate connections. Three full-scale specimens with beam slope angles of 0°, 10°, and 20° were tested under cyclic loading. The results showed that the proposed stiffened connection effectively shifted the stress concentration from the heel and toe regions toward the reduced beam section. The 10° specimen exhibited the best ductility performance, with a ductility approximately 19% higher than that of the 20° specimen and nearly identical to the orthogonal specimen, demonstrating the effectiveness of the proposed stiffened detail, particularly at moderate beam slopes. Moreover, the effective stiffness of the orthogonal specimen was only about 8% higher than that of the 20° sloped specimen, indicating that the proposed stiffened connection effectively compensated for the adverse effects of beam inclination while maintaining satisfactory cyclic performance.