Evaluation of Using Strong Column-Weak Beam Requirements in Prequalified Welded Connections in Intermediate Steel Moment Frame

Document Type : Original Article

Authors

1 Faculty of Civil Engineering., Semnan University, Semnan, Iran

2 M.Sc. Structural Engineering, Faculty of Civil Engineering, Semnan University

Abstract

Beams are genarally used to face bendind force and columns are used to face axial load. as the seismic load comes parallely with respect to earth surface. so the column faces the load pependicularly which is very risky for the column. after that load gets distributed to all the beams. for this reason columns must be strong to make the structure more earth quake resistant.Generally column failure is reason of soft story and collapse of structure Also, because of the axial load yield of columns in shear and moment forces cause loss of strength more than beams and other elements. Structural design codes have a requirement for strength column and weak beam in all joints of special moment connection. In this research strength column and weak beam in prequalified moment connection like reduced beam section (RBS), cover plate connection (WFP) and the welded unreinforced flange-welded web (WUF-W) connection in intermediate moment frames studied. Results shown that ignore strung column and weak beam requirements effect function of the connection and cues to plastic hinge formed in a column. This is effect reduce energy abortion, stiffness and bearing capacity of connections. so as a result it was suggested that for better perfomance prequalified welded connections in intermediate steel moment frame controlled strong columns weak beams requirements.

Keywords

Main Subjects


[1]Heydari, M. and Ahangar, M. (2016). Magnification of code 2800. Tehran: Serie omran, 84.
[2] Code 10 (2012). Design and Construction Provisions For Structural Steel Buildings. Tehran: Toseh iran, 241-256.
[3]AISC 341-10 (2010). Seismic Provisions For Structural Steel Buildings. Chicago: Illinois.
[4]ACI 318-14 (2014). Building code requirements for structural concrete. Farmington Hill.
[5]Code 9 (2012). Design and Construction Provisions For Structural Reinfoced Concrete Buildings. Tehran: Toseh iran, 333.
[6]Euro code 8 (2004), Design of Structures for Earthquake Resistance-Part1: General rules, seismic actions and rules for buildings. Bruxelles.
[7]GB50011-2010 (2010). Chinese Code for seismic design of buildings. Beijing.
[8]Turkish Earthquake Code (TEC-2007) (2007). Regulations on structures constructed in disaster regions Ministry of Public Works and Settlement. Ankara.
[9]Sanchez-Zamora, F., Sanchez, J., Qu, B., Pollino, M., and Mosqueda, G. (2014). Mitigation of Soft-Story Failures in Multi-Story Steel Concentrically Braced Frames through Implementation of Stiff Rocking Cores. In: Structures Congress, 2073-2083.
[10]Qu, B., Sanchez-Zamora, F., Pollino, M. (2014). Mitigation of inter-story drift concentration in multi-story steel Concentrically Braced Frames through implementation of Rocking Cores. Eng. Struct, [online] 70(), 208-217. Available at: https://doi.org/10.1016/j.engstruct.2014.03.032
[11]Hessabi, R. and Mercan, O. (2015). Application of Gyro-Mass Dampers to Mitigate the Seismic Failure in Soft First Story Buildings. In: Structures Congress, 2032-2043.
[12]Chen, Y. Q. and Constantinou, M. C. (1992). Use of Teflon Sliders in a Modification of the Concept of Soft First Storey. Eng. Struct, [online] 6(2), 97-105. Available at: https://doi.org/10.1016/0950-0618(92)90058-7
[13]Benavent-Climent, A. and Mota-Páez, S. (2017). Earthquake retrofitting of R/C frames with soft first story using hysteretic dampers: Energy-based design method and evaluation. Eng. Struct, [online] 137, 19-32. Available at: https://doi.org/10.1016/j.engstruct.2017.01.053
[14]Burnett, C. and McEntee, P. (2009). Manufactured Pre-Engineered Moment Resisting Frames Used in Soft-Story Building Retrofits of Light-Framed Construction. In: Improving the Seismic Performance of Existing Buildings and Other Structures. California: ASCE, 343-349.
[15]Porter, K. and Cobeen, K. (2012). Informing a Retrofit Ordinance: A Soft-Story Case Study. In: Structures Congress, Chicago: ASCE, 1802-1813.
[16]Plumier, A., Doneux, C., Stoychev, L. and Demarcot, T. (2005). Mitigation of Soft Story Failures of R.C. Structures Under Earthquake by Encased Steel Profiles. Advances in Steel Structures, 2, 1193-1198.
[17]Ranjan Sahoo, D. C. and Rai, D. (2013). Design and evaluation of seismic strengthening techniques for reinforced concrete frames with soft ground story. Eng. Struct, [online] 56, 1933-1944. Available at:
https://doi.org/10.1016/j.engstruct.2013.08.018
[18]Gershfeld, M., Chadwell, C., van de Lindt, J., Pang, W., Ziaei, E., Amini, M., Gordon, S. and Jennings, E. (2014). Distributed Knee-Braced (DKB) System as a Complete or Supplemental Retrofit of Soft-story Wood-frame Buildings. In: Structures Congress, Boston: ASCE, 2863-2874.
[19]Agha Beigi, H., Christopoulos, C., Sullivan, T. and Michele Calvi, G. (2014). Gapped-Inclined Braces for Seismic Retrofit of Soft-Story Buildings. J. Struct. Eng., [online] 140(11), 1-11. Available at:
https://doi.org/10.1061/(ASCE)ST.1943-541X.0001006
[20]Kulkarni, S. and Vesmawala, G. (2014). Study of steel moment connection with and without reduced beam section. Case Studies in Structural Engineering, [online]1, 26-31. Available at: https://doi.org/10.1016/j.csse.2014.04.001
[21]Hibbit, Karlsson, Sorenso (2010). ABAQUS Theory Manual. Pawtucket.
[22]FEMA-355D (2000). State of the art report on connection performance. California: Federal Emergency Management Agency.
[23]ATC-24 (1992). Guidelines for Cyclic Seismic Testing of Components of Steel Structures for Buildings. Redwood City: Applied Technology Council.